Dunkirk XEB-4 Operations Instructions Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
EXAMPLE 1: Boiler Located In Unconfined Space
An unconfined space is defined as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour of the total input rating of all
appliances installed in that space.
If your boiler is in an open area (non-partitioned basement) in a conventional house, the air that leaks through the cracks around doors and
windows will usually be adequate to provide air for combustion. The doors should not fit tightly. Do not caulk the cracks around the win-
dows.
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_
Equipment located in buildings of tight construction shall be provided with air for combustion, ventilation, and dilution of flue
gases using the methods described in example 2 (below) or shall be specially engineered. The authority having jurisdiction must
approve specially engineered installations, a building of tight construction is defined as: 1) walls exposed to the outdoor atmo-
sphere have a continuous water vapor retarder with a rating of one perm or less with openings gasketed or sealed; and 2) openable
windows and doors which meet the air leakage requirements of the International Energy Conservation Code, Section 502.1.4; and
3) caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between
wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, and at other openings.
EXAMPLE 2: Boiler Located in Confined Space
1. All Air from Inside the Building: The confined space shall be provided with two permanent openings communicating directly with
an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The
total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Eachopen-
ing shall have a minimum free area of one square inch per 1,000 Btu per hour of the total input rating of all gas utilization equipment in
the confined space, but not less that 100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of the
bottom of the enclosure. The minimum dimension of air openings shall not be less than 3 inches (see Figure 3A).
Figure 3A - Boiler Located in Confined Space
f
Chimney
Or
GasVent
Vent Pipe_
) Openings
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 35 36

Comments to this Manuals

No comments